The chapter guide on Alternating Current for JEE treats transformers in one section and mentions the generator only as the source. Yet these two machines produce a steady stream of short questions: the peak emf of a rotating coil, the time at which the emf first reaches a given value, the secondary current of a step-down transformer, the efficiency of a real one, the power lost in a transmission line, and the statement-reason questions that test why the grid works the way it does. This post gives them the room they need. It starts from Faraday's law, derives the generator emf, builds the transformer relations from the same law, and then works the problem families one at a time.
Both machines are applications of electromagnetic induction. If the idea of flux linkage still feels unsteady, read Electromagnetic Induction for JEE and Motional EMF and Eddy Currents for JEE first. For the circuit side, in particular the phasor method and power factor, the companion post is AC Phasor Diagrams and Power Factor for JEE. All the numerical examples below were checked by computation.
What this post covers
| Part | Question types |
|---|---|
| AC generator | Emf of a rotating coil, frequency, rms value, torque and power |
| Ideal transformer | Voltage, current and turns ratios; multiple secondaries; reflected load |
| Real transformer | Losses, laminated core, efficiency at different loads |
| Transmission | Why high voltage, line loss, voltage at the receiving end |
| Reasoning questions | Statement-reason and multiple-correct on the above |
These topics are in the JEE Main syllabus under alternating current and electromagnetic induction.
The AC generator
A generator converts mechanical work into electrical energy. A coil of $N$ turns and area $A$ rotates at angular speed $\omega$ about an axis perpendicular to a uniform magnetic field $B$. The flux through it is $$\Phi=NBA\cos\theta,\qquad \theta=\omega t$$ when the time is measured from the instant the coil's plane is perpendicular to the field (the normal parallel to $B$). Faraday's law gives the emf $$\varepsilon=-\frac{d\Phi}{dt}=NBA\omega\sin\omega t=\varepsilon_0\sin\omega t$$ with the peak emf $\varepsilon_0=NBA\omega$.
Three details decide most questions:
- The emf is largest when the flux is zero. The flux is largest when the coil's plane is perpendicular to the field, and at that instant the emf is zero. The emf is largest when the plane is parallel to the field, when the sides of the coil cut the field lines at right angles to them. If the question starts the clock with the plane parallel to the field, the emf is $\varepsilon_0\cos\omega t$ instead.
- The peak emf scales as $N$, $B$, $A$ and $\omega$. Doubling the speed doubles both the frequency and the peak emf. Doubling the number of turns doubles the emf but not the frequency. The shape of the coil does not matter, only its area.
- The frequency is $f=\frac{\omega}{2\pi}$. A coil turning at 3000 rotations per minute turns 50 times per second and so produces a 50 Hz emf. A coil with $p$ pairs of poles in the field gives $p$ cycles per rotation.
The rms emf is $\frac{\varepsilon_0}{\sqrt2}$. When the generator drives a load, a current flows, the coil experiences a magnetic torque opposing its rotation (Lenz's law in a mechanical form), and the mechanical power you put in is what appears as electrical power. For a coil carrying current $i$ at angle $\theta$ the torque has magnitude $NBAi\sin\theta$ in the same sense as the emf expression, so the instantaneous mechanical power $\tau\omega$ equals $\varepsilon i$. If it were otherwise, energy would not be conserved.
Slip rings and commutator. An AC generator takes the current out through two slip rings, each joined to one end of the coil, so the output alternates. A DC generator uses a split-ring commutator, which reverses the connections each half turn so that the external current has a constant direction, though it still pulsates in magnitude.
Using a bar magnet instead. In real power stations the field system often rotates inside a fixed coil. The emf relations are the same because only the relative motion of coil and field matters.
Also read: Transformers and AC Generators in Telugu: JEE Main Physics
The ideal transformer
A transformer has two coils wound on a common soft-iron core, a primary of $N_p$ turns connected to the AC source and a secondary of $N_s$ turns connected to the load. The alternating primary current sets up an alternating flux in the core, and because the core guides almost all of it through both coils, the same flux $\Phi$ links each turn of each coil. By Faraday's law $$V_p=N_p\frac{d\Phi}{dt},\qquad V_s=N_s\frac{d\Phi}{dt}\quad\Longrightarrow\quad \frac{V_s}{V_p}=\frac{N_s}{N_p}$$ For an ideal transformer (no losses, perfect flux linkage, no resistance in the windings) the output power equals the input power, so $V_pI_p=V_sI_s$ and $$\frac{V_s}{V_p}=\frac{N_s}{N_p}=\frac{I_p}{I_s}$$ A step-up transformer has $N_s>N_p$: higher voltage, smaller current. A step-down transformer has $N_s<N_p$: lower voltage, larger current. Neither changes the power, and neither changes the frequency.
The peak flux. In an ideal primary the applied voltage balances the induced emf, so $V_{0p}=N_p\omega\Phi_0$ and the peak core flux is $\Phi_0=\frac{V_{0p}}{N_p\omega}$ where $V_{0p}$ is the peak primary voltage. This is why the core cross-section is chosen big enough that the core does not saturate.
Reflected resistance. A load $R_L$ on the secondary appears to the source as $$R_{\text{in}}=\frac{V_p}{I_p}=\frac{V_s\,N_p/N_s}{I_s\,N_s/N_p}=R_L\left(\frac{N_p}{N_s}\right)^2$$ This is the basis of impedance matching. A step-down ratio of $10:1$ makes a load of $10\ \Omega$ look like $1000\ \Omega$ to the source. The factor is the square of the turns ratio, an easy factor to forget.
More than one secondary. If a transformer has several secondaries, the primary supplies the total power: $V_pI_p=\sum V_{s}I_{s}$ (for an ideal transformer and loads at unity power factor). Each secondary voltage is fixed by its own turns ratio, and the primary current is the sum of the power divided by $V_p$. Adding the secondary currents directly is a mistake.
What a transformer cannot do. It does not work with steady direct current, since a constant flux induces no emf in the secondary. It does not raise power. It does not change the frequency. A question that says "a transformer is connected to a 12 V battery" has an output of zero after the initial transient.
The real transformer: four losses
A real transformer is not ideal, and efficiency $\eta=\frac{P_{\text{out}}}{P_{\text{in}}}$ is less than one. The losses are:
- Copper loss. The windings have resistance, so $I^2R$ heating occurs in both coils. It grows as the square of the load current, so it is small at light load and large at heavy load. It is reduced by thick wire.
- Eddy-current loss. The changing flux induces circulating currents in the iron core itself. The core is built from thin insulated laminations, so that each current path is small and the loss falls steeply.
- Hysteresis loss. The core is magnetised and demagnetised every cycle, and each cycle dissipates energy equal to the area of the $B$-$H$ loop. A soft iron alloy with a narrow loop reduces the loss.
- Flux leakage. Some flux from the primary does not link the secondary. A closed core of high permeability, with the coils wound one over the other, reduces it.
Hysteresis and eddy-current losses (together called iron or core losses) depend on the supply voltage and frequency, not on the load. So at no load the transformer already wastes its iron loss; at full load the copper loss adds to it. A frequently asked question compares the efficiency at full and half load, which is Example 12 below.
Transmission of electrical power
A power station delivering power $P$ at voltage $V$ sends a current $I=\frac PV$ through the line (taking unit power factor). The line resistance $R$ causes a loss $$P_{\text{loss}}=I^2R=\frac{P^2R}{V^2}$$ So for the same delivered power and line, the loss falls as the square of the transmission voltage. Raising the voltage tenfold cuts the loss a hundredfold. This is the one and only reason for step-up transformers at the power station: they make high-voltage transmission possible. A step-down transformer at the other end lowers the voltage to a safe value for use, with a correspondingly larger current in the secondary.
There are three further points that students get wrong.
- The line loss is measured as a fraction by $\frac{P_{\text{loss}}}{P}=\frac{PR}{V^2}$. This fraction also falls as $\frac{1}{V^2}$.
- The voltage drop along the line is $IR$ and is a small fraction of the transmission voltage. The voltage at the receiving end is the sending voltage minus $IR$ (for a resistive load).
- The loss in the line depends on the current in the line, so it is the voltage at which the line operates that matters, not the voltage the consumer finally uses.
Worked examples
Example 1 (easy, numerical). A step-down transformer has a primary voltage of 2200 V and a secondary voltage of 220 V. The primary has 4000 turns. Find the number of secondary turns and, for a secondary current of 20 A, the primary current (ideal transformer).
Solution. $\frac{N_s}{N_p}=\frac{220}{2200}=\frac1{10}$, so $N_s=400$ turns. The primary current is $I_p=I_s\frac{N_s}{N_p}=20\times\frac1{10}=2$ A. Check: input power $2200\times2=4400$ W, output $220\times20=4400$ W. Answer: 400 turns and 2 A.
Example 2 (easy to medium, numerical). A transformer is 90% efficient. It takes its input from a 220 V mains and delivers 22 V at 10 A. Find the primary current in amperes to two decimals.
Solution. Output power $=22\times10=220$ W. Input power $=\frac{220}{0.9}=244.4$ W. The primary current is $I_p=\frac{244.4}{220}=1.11$ A. For an ideal transformer it would have been $\frac{220}{220}=1$ A; the real one takes 11% more. Answer: 1.11 A.
Example 3 (easy to medium, numerical). A coil of 100 turns and area $0.05\ \text{m}^2$ rotates in a uniform field of 0.2 T at 50 rotations per second. Find the peak and the rms emf.
Solution. $\omega=2\pi\times50=314.16$ rad s$^{-1}$. $\varepsilon_0=NBA\omega=100\times0.2\times0.05\times314.16=314.2$ V. The rms emf is $\frac{314.2}{\sqrt2}=222.1$ V. Answer: 314 V and 222 V. The rms value is within 1% of 220 V, which suggests a mains-type design.
Example 4 (medium, numerical). A generator coil begins to rotate from the position where its plane is perpendicular to the field. The frequency is 50 Hz. After how much time, in seconds, does the emf first reach half its peak value?
Solution. From this position the emf is $\varepsilon_0\sin\omega t$. Set $\sin\omega t=\frac12$, so $\omega t=\frac\pi6$ and $t=\frac{\pi/6}{2\pi\times50}=\frac{1}{600}$ s $=1.67$ ms. This is $\frac{T}{12}$ with $T=0.02$ s. Answer: $\frac1{600}$ s. If the coil started with the plane parallel to the field the emf would be $\varepsilon_0\cos\omega t$ and the time to reach half the peak would be $\frac{T}{6}=\frac{1}{300}$ s instead.
Example 5 (medium, numerical). A power station delivers 5 MW through a line of total resistance $10\ \Omega$. Find the power lost in the line, as a percentage of 5 MW, if the transmission voltage is 50 kV and if it is 10 kV.
Solution. At 50 kV, $I=\frac{5\times10^6}{5\times10^4}=100$ A, and the loss is $100^2\times10=100$ kW, which is $\frac{100}{5000}=2\%$. At 10 kV, $I=500$ A and the loss is $500^2\times10=2.5$ MW, which is 50%. Answer: 2% and 50%. The voltage went down by a factor of 5, so the loss rose by $5^2=25$; this is the $\frac1{V^2}$ law at work.
Example 6 (medium, single correct). A transformer has a primary of 220 V. One secondary delivers 110 V at 2 A and another delivers 22 V at 5 A, both to resistive loads. Assuming it is ideal, the primary current is
(A) 7 A (B) 1.5 A (C) 0.5 A (D) 3 A
Solution. Total secondary power $=110\times2+22\times5=220+110=330$ W. Then $I_p=\frac{330}{220}=1.5$ A. Answer: (B). The trap is to add the secondary currents (7 A) or to use only one of the secondaries.
Example 7 (medium, numerical). A transformer steps a voltage down in the ratio $10:1$ and supplies a $10\ \Omega$ resistor. What resistance does the source see across the primary?
Solution. The reflected resistance is $R_{\text{in}}=R_L\left(\frac{N_p}{N_s}\right)^2=10\times10^2=1000\ \Omega$. Check with voltages: if the primary voltage is 100 V, the secondary is 10 V, the secondary current is 1 A, the output power is 10 W, and for an ideal transformer the primary current is $\frac{10}{100}=0.1$ A. The source sees $\frac{100}{0.1}=1000\ \Omega$. Answer: 1000 $\Omega$.
Example 8 (medium, numerical). The primary of an ideal transformer has 1000 turns and is connected to a 220 V (rms), 50 Hz mains. Find the peak value of the magnetic flux in the core in milliweber to two decimals.
Solution. The peak primary voltage is $220\sqrt2=311.1$ V. Then $\Phi_0=\frac{V_0}{N\omega}=\frac{311.1}{1000\times314.16}=9.90\times10^{-4}$ Wb $=0.99$ mWb. Answer: 0.99 mWb. A smaller number of turns would need a larger flux for the same voltage, which is why a transformer's primary cannot have too few turns.
Example 9 (hard, numerical). A rectangular coil of 200 turns and area $0.02\ \text{m}^2$ rotates at $100\ \text{rad s}^{-1}$ in a field of 0.5 T, and is connected to a total resistance of $10\ \Omega$ (the coil and external circuit together). Find the peak emf, the average electrical power, and the average torque the agent turning the coil must supply.
Solution. $\varepsilon_0=NBA\omega=200\times0.5\times0.02\times100=200$ V, so the peak current is $\frac{200}{10}=20$ A. The average power is $\tfrac12\varepsilon_0I_0=\tfrac12\times200\times20=2000$ W, or $I_{\text{rms}}^2R=\left(\frac{20}{\sqrt2}\right)^2\times10=2000$ W. In steady rotation the mechanical power equals this, so the average torque is $\frac{P}{\omega}=\frac{2000}{100}=20$ N m. The peak torque is $NBAI_0=200\times0.5\times0.02\times20=40$ N m, twice the average, as expected for a torque proportional to $\sin^2\omega t$. Answer: 200 V, 2000 W, 20 N m.
Example 10 (hard, multiple correct). An ideal step-up transformer has 100 turns in the primary and 1000 in the secondary. The primary is connected to a 220 V, 50 Hz supply, and a resistive load of $2200\ \Omega$ is connected across the secondary. Which statements are correct?
(A) The secondary voltage is 2200 V. (B) The primary current is 10 A. (C) The output power is 2200 W. (D) The frequency of the secondary voltage is 500 Hz.
Solution. $V_s=220\times10=2200$ V, so (A) is correct. The secondary current is $\frac{2200}{2200}=1$ A and the power $2200\times1=2200$ W, so (C) is correct. For an ideal transformer the input power is the same, giving $I_p=\frac{2200}{220}=10$ A, which makes (B) correct. A transformer does not change the frequency, so (D) is false. Answer: (A), (B) and (C). The $\frac{I_p}{I_s}=10$ ratio is the inverse of the voltage ratio.
Example 11 (hard, single correct). A generator coil gives a peak emf of 200 V when it rotates at 50 Hz. If the speed is halved with the field and coil unchanged, the rms emf in the output is closest to
(A) 141 V (B) 100 V (C) 70.7 V (D) 50 V
Solution. The peak emf is proportional to $\omega$, so it falls to 100 V; the frequency becomes 25 Hz. The rms emf is $\frac{100}{\sqrt2}=70.7$ V. Answer: (C). Option (B) forgets the $\sqrt2$, and (A) forgets that the peak changes along with the frequency.
Example 12 (hard, numerical). A transformer delivers 10 kW at full load. Its copper loss at full load is 400 W and its iron loss is 300 W. Find its efficiency at full load, and at half the full load (the iron loss being unchanged), in percent to two decimals.
Solution. At full load the input power is $10000+400+300=10700$ W, so $\eta=\frac{10000}{10700}=93.46\%$. At half load the output is 5000 W and the current is half, so the copper loss is a quarter of 400 W, which is 100 W. Input is $5000+100+300=5400$ W and $\eta=\frac{5000}{5400}=92.59\%$. Answer: 93.46% and 92.59%. The efficiency is highest when the copper loss equals the iron loss; here that would be at a load below full load.
Example 13 (hard, numerical). A generator produces 110 kW at 2.2 kV. A transformer steps this up to 22 kV for a line of total resistance $44\ \Omega$. Taking unity power factor, find the line current, the power lost in the line, and the power received at the far end. A step-down transformer there delivers the power at 220 V; find its secondary current.
Solution. At 22 kV, $I=\frac{110\times10^3}{22\times10^3}=5$ A. The loss is $5^2\times44=1100$ W, which is 1% of the power sent. The power received is $110000-1100=108900$ W. The step-down transformer (assumed ideal) delivers 108.9 kW at 220 V, so its secondary current is $\frac{108900}{220}=495$ A. The line voltage at the far end is $22000-5\times44=21780$ V, so the step-down ratio is $\frac{21780}{220}=99:1$. Answer: 5 A, 1.1 kW, 108.9 kW, 495 A. Without the step-up, the line would carry $\frac{110000}{2200}=50$ A and lose $50^2\times44=110$ kW, all of the power sent.
Common traps
Reading a transformer's efficiency from the turns ratio. The turns ratio fixes the voltage ratio of an ideal transformer, not its efficiency. Real efficiency needs the powers.
Believing a step-up transformer increases power. It raises voltage and lowers current by the same factor. A statement that it "produces more energy" is false.
Using the maximum-emf instant as the zero-flux instant the wrong way round. The emf is zero when the plane is perpendicular to the field (flux maximum), and largest when the plane is parallel to the field. Reverse them and every timing answer is off by a quarter period.
Putting the clock at the wrong position. A coil started with its plane parallel to $B$ gives $\varepsilon_0\cos\omega t$. A question about the time to reach half the peak then has a different answer from the sine form.
Forgetting that frequency changes with speed. Halving the rotation speed halves both $f$ and $\varepsilon_0$. Students who reduce only the frequency miss the effect on the emf.
Squaring the wrong ratio. The reflected resistance goes as $\left(\frac{N_p}{N_s}\right)^2$, with the primary turns on top for a load on the secondary. Inverting gives a thousandth of the correct value for a $10:1$ ratio.
Adding currents of different secondaries. Each secondary current is at a different voltage; only the powers add.
Applying a DC source to a transformer. The steady flux induces nothing in the secondary. Only a change of flux at the start produces a short pulse.
Taking the line loss as dependent on the consumer's voltage. The loss is in the line carrying the high-voltage current. The final low voltage after the step-down transformer does not enter into it.
Mixing up the reasons for laminations and for a soft-iron core. Laminations reduce eddy-current loss; a soft-iron core (low coercivity) reduces hysteresis loss. A statement-reason question may swap the two.
Confusing the fractional power loss with the fractional voltage drop. The fraction of power lost is $\frac{I^2R}{P}=\frac{PR}{V^2}$, which is a power ratio. A question that asks for the percentage of power lost should not be answered with $\frac{IR}{V}$ unless you have checked that the two agree for the given power factor.
Using the peak emf in the average-power formula. For a resistive load the average power is $\frac{\varepsilon_0^2}{2R}$. Using $\varepsilon_0^2/R$ doubles the result.
A one-page recap
| Item | Result |
|---|---|
| Generator emf | $\varepsilon=NBA\omega\sin\omega t$ (clock from plane perpendicular to $B$) |
| Peak emf, rms | $\varepsilon_0=NBA\omega$ ; $\frac{\varepsilon_0}{\sqrt2}$ |
| Frequency | $f=\frac{\omega}{2\pi}$ |
| Mechanical power | $\tau\omega=\varepsilon i$ |
| Ideal transformer | $\frac{V_s}{V_p}=\frac{N_s}{N_p}=\frac{I_p}{I_s}$ |
| Reflected resistance | $R_{\text{in}}=R_L\left(\frac{N_p}{N_s}\right)^2$ |
| Peak core flux | $\Phi_0=\frac{V_{0p}}{N_p\omega}$ |
| Efficiency | $\eta=\frac{P_{\text{out}}}{P_{\text{in}}}$ ; copper loss $\propto I^2$, iron loss fixed |
| Line loss | $\frac{P^2R}{V^2}$ |
| Transformer cannot | work on dc, change frequency, or raise power |
Also read: JEE Main Physics Preparation Strategy: Plan and Practice
How to practise this topic
The questions on these machines sit in the Alternating Current chapter tests (some in the Electromagnetic Induction tests as well). Start with Alternating Current, test 1, then test 4 and test 5. For the induction side, use Electromagnetic Induction, test 1. Each test has 15 questions in 36 minutes. The study chapters are in English, Hindi and Telugu for Alternating Current, and English, Hindi and Telugu for Electromagnetic Induction.
A seven-day plan:
- Day 1. The generator: derive the emf yourself, then solve ten problems on peak, rms and the timing of the emf for both starting positions.
- Day 2. Generator with a load: torque, power and Lenz's law as energy conservation.
- Day 3. Ideal transformers: voltage, current, turns, multiple secondaries and reflected resistance.
- Day 4. Real transformers: losses, laminations, efficiency at different loads.
- Day 5. Transmission: line loss as a percentage at three voltages, the receiving-end voltage, a two-transformer chain as in Example 13.
- Day 6. Statement-reason and multiple-correct questions on all of the above; the method for a quick numerical check is in calculation speed and approximation.
- Day 7. A timed chapter test, an error log, and a second attempt at every miss.
Then mix with a Physics practice test such as JEE Main Physics Practice Test 07 and a full paper such as JEE Main Mock 6. Full mocks, practice tests and chapter tests are part of the Pro Pass; the free JEE Main mini mock needs no sign-up. The cluster overview is Magnetism, EMI and Alternating Current for JEE.
Frequently asked questions
Why is the emf of a generator zero when the flux through the coil is maximum?
The emf depends on the rate of change of flux, not on the flux itself. At the position of maximum flux the flux curve is at its peak and is momentarily not changing, so the rate is zero. The rate is greatest when the flux passes through zero, which is when the coil's plane is parallel to the field.
Why does a transformer not work on direct current?
A steady current in the primary produces a steady flux, and a steady flux induces no emf in the secondary. The transformer relies on a changing flux. For this reason a battery cannot be used to run a transformer, though a switch that opens and closes will make a pulse.
How do laminations reduce eddy-current loss?
Thin insulated layers break the core into narrow sheets, so the induced eddy currents are forced into small loops with high resistance and small current. The power lost in each loop depends on the square of the induced emf, and a smaller loop encloses less changing flux, so the total loss falls greatly.
Why is high voltage used for transmission and not high current?
For a given power, $P=VI$. A larger $V$ means a smaller $I$, and the heat lost in the line is $I^2R$. Transmitting at high current would waste most of the power in the wires. Transformers make the voltage change easy, which is why alternating current is used on the grid.
What is the efficiency of an ideal transformer?
One hundred per cent, since an ideal transformer has no losses. Real large transformers have efficiencies of the order of 95 to 99 per cent, though a JEE question will always give you the powers or the losses to compute it.
Does the secondary current of a transformer depend on the primary?
It is set by the load, not by the primary. The load on the secondary fixes the secondary current through $I_s=\frac{V_s}{R_L}$, and the primary current then adjusts so that $V_pI_p=V_sI_s$. This is why a lightly loaded transformer draws little current from the mains.
How can I recognise a statement-reason question about transmission?
It usually pairs a true statement (power is transmitted at high voltage) with a true but wrong reason (transformers are easy to use). The correct reason is the smaller current and hence the smaller $I^2R$ loss. Check each part separately, then ask whether the reason explains the statement.